Connecting the trigger input terminal
To input trigger signals from an external device, wire the cable to the EXT TRIG terminal as shown below.
Use a flat-blade screwdriver to push the minus (–) button above the terminal, insert the wire and then remove
the screwdriver.
After finishing wiring, lightly pull the wire to make sure it does not come out.
Internal Equivalence Circuit
Item
Description
Number of channels
1
Input voltage range
0 to +24V max. (single-ended
ground input)
Threshold level
+2.5V
Hysteresis
Approx. 0.5 V (+2.5 to +3 V)
Connecting the alarm output terminal
To output alarm signals, wire the cable to the ALARM terminal as shown below.
Use a flat-blade screwdriver to push the minus (-) button above the terminal, insert the wire and then remove
the screwdriver.
After finishing wiring, lightly pull the wire to make sure it does not come out.
20
Item
Description
Number of channels
1
Maximum rating
DC30V 0.5A or less
Connecting the External I/O Terminal