z Starting DC brake
Group
Function
group 1
ƒ
ƒ
Display
Parameter Name
Setting
Range
Default
Unit
F12
[DC Brake start voltage]
-
0 ~ 200
50
%
F13
[DC Brake start time]
-
0 ~ 60
0
sec
F12: It sets the level as a percent of H33 – [Motor rated current].
F13: Motor accelerates after DC voltage is applied for the set time.
☞Caution:
If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor
overheating and damage to the motor.
Freq.
F13
t
F12
Voltage
Run
command
Setting F12 or F13 to 0 will disable Starting DC brake.
t: After F13 - [DC Brake start time], the frequency is increasing after DC voltage is applied until the
time t.
z DC brake at a stop
Group
Display
Parameter Name
Setting
Range
Default
Unit
%
Function
group 1
F12
[DC Brake start voltage]
-
0 ~ 200
50
I/O group
I19
[Multi-function Input
terminal P3 Function select]
11
0 ~ 25
2
ƒ
ƒ
ƒ
F12: It sets the level as a percent of H33 – [Motor rated current].
Select a terminal to issue a command of DC brake at a stop among P1 to P8.
If P3 terminal is set for this function, set I19 to 11 {DC brake during stop}.
☞ Caution:
If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor
overheating and damage to the motor.
Voltage
F12
P3
Run
command