Download chapter 1 - InverterDelta
Transcript
z Protective function Over Voltage, Under Voltage, Over Current, Ground Fault current detection, Inverter Trip Overheat, Motor Overheat, Output Phase Open, Overload Protection, Communication Error, Loss of Speed Command, Hardware Fault, Fan trip Alarm Stall prevention, overload Momentary Below 15 msec: Continuous operation (should be within rated input voltage, rated Power output power.) Loss Above 15 msec: Auto restart enable z Environment Protection degree Ambient temp Storage temp Humidity Altitude/Vibration Atmospheric pressure Location IP 20 -10°C ~ 50°C -20°C ~ 65°C Below 90% RH (no condensation) Below 1,000m, 5.9m/sec2 (0.6G) 70~106 kPa Protected from corrosive gas, combustible gas, oil mist or dust 15.2 Temperature Derating Information z Load and ambient temperature classified by the Carrier Frequency % of Drive Rated Amps 100% 90% 80% 72% 70% 60% 58% 50% 40℃ Rating 40% 41℃ ~ 50℃ Rating 30% 20% 10% 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Carrier Frequency in kHz * Note) 1) The above graph is only applied when the inverter is operated in the allowable temperature. Pay attention to the air cooling when the inverter is installed in a panel box, and the inside temperature should be within an allowable temperature range. 2) This derating curve is based on inverter current rating when rated motor is connected. 15-3