Download Model 940 USERS MANUAL
Transcript
Nominal Bus Voltage (Vbus) The Nominal Bus Voltage can be calculated by multiplying the Nominal AC mains voltage supplied by 1.41. When using a model with the suffix “S1N” where the mains are wired to the “Doubler” connection, the Nominal Bus Voltage will be doubled. Example: If the mains voltage is 230VAC, Vbus = 230 x 1.41 = 325V This value is the initial voltage for the drive and the correct voltage will be calculated dynamically depending on the drive’s incoming voltage value. Rotor Moment of Inertia (Jm) From motor manufacturer or nameplate. Note Round the calculated result to 3 significant places. Maximum Motor Speed in RPM This is also listed as “Speed @ Vt” (motor speed at the terminal voltage rating). The maximum motor speed will typically be a round even value between 1000 and 6000 RPM. Number of Poles This is a positive integer number that represents the number of motor poles, normally 2, 4, 6 or 8. 5.6.3.2 For motors equipped with incremental encoders only: Encoder Line Count The Encoders for servomotors normally have Line Counts of 1000, 1024, 2000, 2048, 4000, or 4096. The Encoder Line Count must be a positive integer and must be prequadrature. Index pulse offset. Enter 0 (zero) Index marker pulse position. This field is reserved for backward compatibility. All PositionServo drives determine actual marker pulse position automatically. 32 S94P01A