Download MULTIV SERVICE
Transcript
Operation detail 3. Operation detail (1) The function of main control ■ Time Delay Safety Control • 5 sec... Vertical air flow direction control louvers open in 5 seconds to prevent noise between louvers and wind. • 5 sec... The 4-way valve is ceased for 5 sec. to prevent the refrigerant-gas abnormal noise when the Heating operation is OFF or switched to the other operation mode when compress is off. While compressor is running, it takes 3~5 seconds to switch. ■ Auto Swing Control • This function is to swing the louver up and down automatically. ■ Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. ■ Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following Intake Air Temperature COMP. ON (SET TEMPERATURE +0.5°C) COMP. OFF (SET TEMPERATURE -0.5°C) INDOOR FAN Selecting fan speed More than More than 3 minutes 3 minutes Low Selecting fan speed Low Selecting fan speed Service Manual 47