Self-diagnosis function
Fault diagnosis and Trouble shooting guide
Error Display
No.
01
02
06
Error Item
Air temperature sensor
of the indoor unit
Inlet pipe temperature
sensor of the indoor unit
Meaning
Major Error Occurrence Cause
Short or open of
indoor unit sensor
• Poor sensor connection
• Short or open of sensor
• Defective indoor PCB
Outlet pipe temperature
sensor of the indoor unit
Failure Checking Method
Check connection status between
PCB and sensor
No
Is connection status of
the sensor normal?
Reconnect the sensor at
accurate position
Yes
Pull the sensor out and then measure
sensor resistance
No
Is sensor resistance
normal?
Yes
Replace the sensor
* See the Temperature Resistance Table
Check the indoor
unit PCB
262
Trouble Shooting Guide