PICK VARIABLE FLOW SERVICE MANUAL Malfunction in the pump look check valve Capacity of heater is exceeded Steam inlet pressure varies Steam valve has a jerky motion Faulty temperature controller Boiler or supply not adequately sized to provide enough steam to accommodate all demands in the steam system Steam quality may be poor (excess condensate entrained in system) Steam valve packing gland too tight Air leak in the control line Steam valve oscillates *PID- Proportional Integral Derivative, the tuning parameters on some electronic and pneumatic temperature controllers Inspect and repair check valve as necessary Consult Pick Heaters for heater upgrade information Repair or replace controller Check steam supply sizing and boiler for pressure fluctuations Install a drip leg with a steam trap upstream of the strainer, to maintain high quality steam at the heater. Adjust steam valve stem packing gland -Use Soap solution to detect any leaks -Repair leaks or replace line Optional temperature Tune the controller per controller not properly tuned controller manual. *(PID Parameters) Refer to detailed Injection tube problem instructions for Stuck piston disassembly and Plugged Orifices inspection of the heater Broken spring and injection tube -Bleed air from the Air or gas trapped in a high system point of the supply or the discharge piping creating an -Remove surge tank -Install automatic air unstable condition vent valve(s) at system high points Water and steam pressures Check operating too close together pressures Reduce water pressure or increase steam pressure 21 22 See Installation Manual 21 21 12-14 23 7