PICK VARIABLE FLOW SERVICE MANUAL
Steam quality may be poor
(excess condensate
entrained in steam
Steam control valve
positioned less than 20%
open (operating below
minimum turndown)
Steam control valve moves
too fast (only with nonstandard or faulty
temperature controller)
Injection tube problem
Crack or hole in steam flow
Steam control valve moves
too fast due to use of valve
positioner(s)
Steam valve opening
pressure out of adjustment
Valve packing gland too
tight
Unstable steam pressure
reducing valve upstream of
the system
-Examine the steam
system, correcting any
deficiencies
-Install a drip leg with
steam trap, upstream of
the strainer, to maintain
high quality steam at
the heater
Check steam valve
travel when operating.
Valve must be open
more than 20% open.
Consult Pick Heaters
about a smaller or dual
steam valve
arrangement
The temperature
controller should be
tuned to allow 7-10
seconds for full valve
travel
Refer to detailed
instructions for
disassembly and
inspection of the heater
and injection tube.
Replace piston, spring
or injection tube if
required
Repair or replace inlet
house.
CONSULT FACTORY
Remove valve
positioner(s)
See
installation
manual
Adjust valve according
to steam valve
instruction manual
Adjust packing gland
according to valve
manual
20
21
11-13
21
Examine reducing
valve, repair or replace
if necessary
9