Transcript
PICK VARIABLE FLOW SERVICE MANUAL PROBLEM: Noisy Heater Operation. OBSERVATION PROBABLE CAUSE Air trapped in a high point of the cold water supply or the hot water header, creating an unstable condition Distribution branches not connected to the top of water headers USE-POINT control valves opening or closing too rapidly Cross-connection between the hot water line and another water line Water and steam pressures too close together Unstable water pressure valve in system Shock absorber or pulsation dampener device in the system Supply water pressure may be unstable Continued next page ACTION Bleed air from the water system Install automatic air vent valve(s) Check connection of distribution branches, re-pipe if necessary or Add automatic air bleeds at system high points -Readjust rapid-acting control valves -Adjust or repair valves as necessary to allow smooth operation -Eliminate sources of water pressure spikes or upsets -Visually trace all lines to locate possible crossconnections -Eliminate the crossconnection with installation of check valves or other valving -Check operating pressures -Reduce water pressure or increase steam pressure -Observe operation of all valves with steam to the heater turned off -Adjust or replace faulty valves as necessary Remove all shock absorber devices (surge tank) -With steam off, inspect water supply system or pressure, and correct as necessary -Install water pressure control valve if required PAGE 23 23 23 8