EC-Control User Manual - Installation USB relay box (external signalling of failures) UPS Optional Optional Optional IP address, e.g. 192.168.0.1 Ethernet / TCP/IP Ethernet switch IP address, e.g. IP address, e.g. IP address, e.g. 192.168.0.2 192.168.0.3 192.168.0.4 Fig. 2-2 Large size fab Several Ethernet/RS485 interface converters are connected via a switch to the network card of the computer. The individual network segments are called subnets. Monitoring of the clean room fans is safeguarded by a UPS (Uninterruptible Power Supply). All fans are connected to the interface converter concerned in either a linear or a star configuration. The printer and a second monitor are optional. Only fans of the same bus system (ebmBUS or MODBUS) are to be connected to each interface converter. However, it is possible to combine different bus systems within one fab. EC-Control currently permits a maximum of four interface converters with MODBUS and a maximum of four interface converters with ebmBUS in one fab. This configuration increases reliability and interrogation rate and is therefore particularly well suited to monitoring large-scale clean room fabs. In this case, it is also advisable to safeguard the computer with a UPS to enable the fab monitoring system to register the fab status without any time delay in the event of power failure. General rule: In fabs with more than 31 fans, it may be necessary to use RS485 repeaters (article no. 25708-1-0174) depending on the type of fan. 12