Transcript
Manual VIPA System 200V Chapter 6 Analog input modules 231-1BD70 - AI 4x12Bit, ±10V, isolated Order data AI 4x12Bit, ±10V, isolated Description The module has 4 inputs that are permanently configured to measure voltage signals (±10V). This module requires a total of 8byte of the process image for the input data (2byte per channel). The measured values are returned in S5 format from Siemens. DC/DC converters and isolation amplifiers are employed to provide electrical isolation for the channels of the module with respect to the backplane bus and between the different channels. Properties • 4 inputs, channels isolated from the backplane bus and from each other (Galvanic isolation of the channels by means of isolation amplifiers) • Permanently configured for voltage measurements • No parameterization required • Suitable for transducers with ±10V outputs VIPA 231-1BD70 [1] Construction 1 [2] 2 [3] [4] 3 Label for the name of the module Label for the bit address with description LED status indicator Edge connector 4 Pin assignment Pin Assignment 1 2 3 4 5 6 7 8 9 10 pos. connection Channel 0 Channel 0 common pos. connection Channel 1 Channel 1 common pos. connection Channel 2 Channel 2 common pos. connection Channel 3 Channel 3 common SM 231 AI 4x12Bit 10V 1 +0 2 M0 3 +1 4 M1 5 +2 6 M2 7 +3 8 M3 9 I0 X 2 3 4 VIPA 231-1BD70 HB97E - SM - Rev. 09/19 6-41