Manual VIPA System 200V
Once
Chapter 9 SM 238C - Combination module
No main counting direction
• The counter counts once starting with the load value.
• You may count forward and backwards.
• The count limits are set to the maximum count range.
• At over- or underrun at the count limits, the counter jumps to the
according other count limit and counts from there on. The gate is
automatically closed.
• To restart the count process, you must create a positive edge of the
gate.
• At interrupting gate control, the count process continuous with the last
recent counter value.
• At aborting gate control, the counter starts with the load value.
Lower count limit
Upper count limit
Counter value
Load value
Valid value range
- 2 147 483 648 (-231)
+ 2 147 483 647 (231-1)
- 2 147 483 648 (-231) to + 2 147 483 647 (231-1)
31
31
- 2 147 483 647 (-2 +1) to + 2 147 483 646 (2 -2)
Interrupting gate control:
counter value
upper
counter limit
overflow
load value
0
lower
counter limit
underflow
time
gate start
gate stop gate start
automatically
gate stop
automatically
Aborting gate control:
counter value
upper
counter limit
overflow
load value
0
lower
counter limit
underflow
gate start
HB97E - SM - Rev. 09/19
gate stop gate start
automatically
gate stop
automatically
time
9-27