Parameters
List of Parameters
p8706[0...1]
CAN Receive PDO 7 / Receive PDO 7
CU230P-2 CAN
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: C(3), T
Scaling: -
Data set: -
Units group: -
Unit selection: -
Min
0000 hex
Max
8000 06DF hex
Factory setting
[0] 8000 06DF hex
[1] 00FE hex
Description:
Sets the communication parameters for CANopen Receive Process Data Object 7 (RPDO 7).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Note:
Corresponds to the CANopen object 1406 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8707[0...1]
CAN Receive PDO 8 / Receive PDO 8
CU230P-2 CAN
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: C(3), T
Scaling: -
Data set: -
Units group: -
Unit selection: -
Min
0000 hex
Max
8000 06DF hex
Factory setting
[0] 8000 06DF hex
[1] 00FE hex
Description:
Sets the communication parameters for CANopen Receive Process Data Object 8 (RPDO 8).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Note:
Corresponds to the CANopen object 1407 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8710[0...3]
CAN Receive Mapping for RPDO 1 / Mapping RPDO 1
CU230P-2 CAN
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: C(3), T
Scaling: -
Data set: -
Units group: -
Unit selection: -
Min
0000 hex
Max
FFFF FFFF hex
Factory setting
0000 hex
Description:
Sets the mapping parameters for CANopen Receive Process Data Object 1 (RPDO 1).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1600 hex + 40 hex * x (x: Drive number 0 ... 7).
Dummy mapping not supported.
The parameter can only be written online when the associated COB ID in p870x is set as invalid.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011