Download Bosch GREENSTAR PLUS Technical data
Transcript
COMMISSIONING 6.2.23 SETTING PARAMETERS AT THE HYBRID CONTROL MODULE 5 6 4 3 2 1 6 720 646 970-36.2ITL Fig. 51 Control module of the hybrid manager [1] [2] [3] [4] [5] [6] Fuse, 5 AT, ceramic, filled with sand Spare fuse Service key connection Rotary selector: turn to scroll, push to select Display Back button Display [5] shows the current status/display code or parameter list. This can be recognised by the letters on the right hand side of the display. • “c”: Parameter list • “e”: Status/display code ▶ With the “Back button”, change between the current status/display code and parameter list. ▶ Scroll through the parameter list with the “Rotary selector”. ▶ Push “Rotary selector” to select any parameter. The selected parameter begins to flash. ▶ Set the required value by turning the “Rotary selector”. ▶ Push “Rotary selector” to confirm and save the new parameter setting. Display code Aa Description Setting the hydraulic system Unit — Standard setting 0 Ab Heat source delay min 20 5 - 120 Ac Heat source delay temperature K 3 1 - 99 A5 External unit control interval min 1 1 - 30 Input range 0 = In series 1 = In parallel (not possible with this system) This determines the function of the pump in the Hybrid Manager. 0= the pump provides water circulation around the central heating circuit(s) - used for all hydraulics described in this document, 1= the pump does not provide water circulation around the central heating circuit(s), for this type of system each heating circuit has its own pump. The HTH (high temperature heat source) delay time given to the boiler if; (The required system flow temperature – the actual system flow temperature) is equal to or less than the set Delta T. The delta temperature used by the delay timer. The temperature difference between the required system flow temperature and the actual system flow temperature that will activate the delay time. The time interval at which the set point is re-calculated, based on changing external influences. Table 21 Parameter list of the hybrid control module 44 6 720 803 687 (2012/11)