EN54 FIREFINDER PLUS
INSTALLATION,COMMISSIONING & OPERATION
12.8.2 Remote Relay Board
In the remote version the Comms In and Out Terminal Block TB9 is cabled to the RS485 Comms
terminal block TB1on the Communications Extender Board (see section 5.12) and can be installed
up to 1.2kms from the FACP.
Note: Can be powered from the panel or an external 27 volt source.
N/0 = Normally Open
COM = Common
N/C = Normally Closed
O/P 1
COM
N/0
N/C
TB1
O/P 2
N/0
COM
N/C
TB2
N/0
O/P 3
COM
N/C
TB3
N/0
COM
N/C
N/0
TB4
O/P 1
COM
O/P 4
N/0
N/C
TB1
N/0
O/P 2
COM
N/C
TB2
N/0
O/P 5
COM
N/C
TB5
O/P 3
COM
N/C
N/0
TB3
N/C
COM
N/C
TB4
O/P 5
N/0
COM
N/C
TB5
N/0
O/P 7
N/0
N/C
COM
O/P 6
COM
N/C
TB6
N/0
O/P 7
COM
N/C
TB7
Fit EOL Termination
Link 1 if Last Module
To TB3 on the Main
on Comms Bus
and/or Zone
TB10 Card
Mimic Card
+ - + -
O/P 8
N/0
TB7
TB6
O/P 4
COM
O/P 6
N/0
COM
N/C
TB8
N/0
O/P 8
COM
N/C
TB8
Address SW
(See Note)
O N ON
TB9
1 2 3 4
SW1
RS485+ SHD RS485+ SHD
RS485RS485-
RS485 COMMS IN / OUT
27 Volts In
(External Supply)
27 Volts Out
(External Supply)
Figure 84: Remote 8 Way Relay Board Front View showing connectors and Address Switch
Relay Connections
Terminal/s
TB1 to 8
Function
N/O = Normally Open,
C = Common
N/C = Normally Closed
Relay 1 to 8
Communications Connections
Terminal
TB9
TB9
Function
RS485+
RS485Shield
RS485+
RS485Shield
Communications In
Communications Out
Note: See Section 17 for Addressing Details (SW1)
Page 59