Other modules 14.2 Watchdog module Parameter Parameter Range of values Default Applicability Mode Disabled write/ read write/ read neg. Toggle 0.1 Hz Toggle 0.5 Hz Toggle 1 Hz Toggle 2 Hz write/ read Module Response to CPU/ Keep last value Set to 00H Set to FFH Keep last value Module Master STOP Parameter description: Mode Disabled: A value that you write to the output byte is not transferred to the input byte. write/ read: A value that you write to the output byte is transferred to the input byte. write/ read neg.: A value that you write to the output byte is inverted and transferred to the input byte. toggle 0.1 Hz; toggle 0.5 Hz; toggle 1 HZ; toggle 2 Hz: Bit 0 (see address space of inputs and outputs) in the input byte of PII toggles (flashes) at the specified frequency. Parameter description: Response to CPU/Master STOP Keep last value: The last value in the output byte of the PIQ is retained. Set to 00H: The value in the output byte of the PIQ is set to 00H. Set to FFH: The value in the output byte of the PIQ is set to FFH. 340 ET 200iSP Operating Instructions, 01/2010, A5E00247483-04