Analog electronic modules 13.8 Representation of analog values Measuring ranges for resistance thermometer Ni 100 standard Table 13- 17 SIMATIC S7 format: Measuring ranges Ni 100 standard in °C and °F Range Ni 100 standard in °F (1 digit = 0.1 °F) decimal hexadec imal 7FFFH > 563.0 32767 7FFFH Overflow B86H 563.0 5630 15FEH Overrange : : : : : 250.1 2501 9C5H 482.1 4821 12D5H 250.0 2500 9C4H 482.0 4820 12D4H : : : : : : -60.0 -600 FDA8H -76.0 -760 FD08H -60.1 -601 FDA7H -76.1 -761 FD07H Ni 100 standard in °C (1 digit = 0.1°C) decimal hexadec imal > 295.0 32767 295.0 2950 : Units Units : : : : : : -105.0 -1050 FBE6H -157.0 -1570 F9DEH < -105.0 -32768 8000H < -157.0 -32768 8000H Nominal range Underrange Underflow Measuring ranges for resistance thermometer Ni 100 climate Table 13- 18 SIMATIC S7 format: Measuring ranges Ni 100 climate in °C and °F Range Ni 100 climate in °F (1 digit = 0.01 °F) decimal hexadec imal 7FFFH > 325.11 32767 7FFFH Overflow 733CH 327.66 32766 7FFEH Overrange : : : : : 25001 61A9H 280.01 28001 6D61H 250.00 25000 61A8H 280.00 28000 6D60H : : : : : : -60.00 -6000 E890H -76.00 -7600 E250H -60.01 -6001 E88FH -76.01 -7601 E24FH : : : : : : -105.00 -10500 D6FCH -157.00 -15700 C2ACH < - 105.00 -32768 8000H < - 157.00 -32768 8000H Ni 100 climate in °C (1 digit = 0.01°C) decimal hexadec imal > 295.00 32767 295.00 29500 : 250.01 Units ET 200iSP Operating Instructions, 01/2010, A5E00247483-04 Units Nominal range Underrange Underflow 299
Related documents
Craftsman 917.259870 Owner`s manual
Acoplador DP/PA, distribuidores de campo activos, DP
Velleman DVM1500 multimeter
Siemens ET 77..UC Operating instructions
5926 KB - Siemens
IQ PRO R210L/350/500
Frigidaire FFPA1022R1 Owner's Manual
SERVICE MANUAL
Dezentrales Peripheriegerät ET 200iSP - Service
DTM Library User Manual - CommDTM ET 200iSP