Analog electronic modules
13.8 Representation of analog values
Measuring ranges for resistance thermometer Ni 100 standard
Table 13- 17 SIMATIC S7 format: Measuring ranges Ni 100 standard in °C and °F
Range
Ni 100
standard in
°F (1 digit =
0.1 °F)
decimal
hexadec
imal
7FFFH
> 563.0
32767
7FFFH
Overflow
B86H
563.0
5630
15FEH
Overrange
:
:
:
:
:
250.1
2501
9C5H
482.1
4821
12D5H
250.0
2500
9C4H
482.0
4820
12D4H
:
:
:
:
:
:
-60.0
-600
FDA8H
-76.0
-760
FD08H
-60.1
-601
FDA7H
-76.1
-761
FD07H
Ni 100
standard in
°C (1 digit =
0.1°C)
decimal
hexadec
imal
> 295.0
32767
295.0
2950
:
Units
Units
:
:
:
:
:
:
-105.0
-1050
FBE6H
-157.0
-1570
F9DEH
< -105.0
-32768
8000H
< -157.0
-32768
8000H
Nominal range
Underrange
Underflow
Measuring ranges for resistance thermometer Ni 100 climate
Table 13- 18 SIMATIC S7 format: Measuring ranges Ni 100 climate in °C and °F
Range
Ni 100
climate in
°F (1 digit =
0.01 °F)
decimal
hexadec
imal
7FFFH
> 325.11
32767
7FFFH
Overflow
733CH
327.66
32766
7FFEH
Overrange
:
:
:
:
:
25001
61A9H
280.01
28001
6D61H
250.00
25000
61A8H
280.00
28000
6D60H
:
:
:
:
:
:
-60.00
-6000
E890H
-76.00
-7600
E250H
-60.01
-6001
E88FH
-76.01
-7601
E24FH
:
:
:
:
:
:
-105.00
-10500
D6FCH
-157.00
-15700
C2ACH
< - 105.00
-32768
8000H
< - 157.00
-32768
8000H
Ni 100
climate in
°C (1 digit =
0.01°C)
decimal
hexadec
imal
> 295.00
32767
295.00
29500
:
250.01
Units
ET 200iSP
Operating Instructions, 01/2010, A5E00247483-04
Units
Nominal range
Underrange
Underflow
299