MRT-Expert (continued)
4. Wire the room sensor into the four-wire Rnet input on the left side of the
unit control module.
5. Change the Control System parameter on Unit Modes screen of BACview
to MRT.
MDT
MDT-Expert
(cont.)
1. Order a BACview remote panel from the factory and plug it into the local
access connection on the front of the unit control module.
2. Disconnect the unit enable potentiometer from terminals 214, 215, and 216
and place a jumper between terminals 213 and 216 on the main terminal
strip.
MRT
1. Remove the jumper between terminals 213 and 216 on the main terminal
strip and connect the unit enable potentiometer to terminals 214, 215, and
216.
2. Disconnect the BACview remote panel from the local access connection on
the front of the unit control module. Leave the room sensor connected.
MDT
1. Remove the jumper between terminals 213 and 216 on the main terminal
MRTstrip and connect the unit enable potentiometer to terminals 214, 215, and
Expert
216.
2. Change the Control System parameter on Unit Modes screen of BACview
to MDT.
3. Disconnect the BACview remote panel from the local access connection on
the front of the unit control module.
MDT-Expert
1. Change the Control System parameter on Unit Modes screen of BACview
to MDT.
MRT
1. Remove the jumper between terminals 213 and 216 on the main terminal
strip and connect the unit enable potentiometer to terminals 214, 215, and
216.
2. Change the Control System parameter on Unit Modes screen of BACview
to MRT.
3. Disconnect the BACview remote panel from the local access connection on
the front of the unit control.
4. Order a room sensor from the factory and wire it into the four-wire Rnet
input on the left side of the unit control module.
MDTMDT
Expert
1. Remove the jumper between terminals 213 and 216 on the main terminal
strip and connect the unit enable potentiometer to terminals 214, 215, and
216.
2. Disconnect the BACview remote panel from the local access connection on
the front of the unit control module.
MRT-Expert
1. Order a room sensor from the factory and wire it into the four-wire Rnet
input on the left side of the unit control module.
2. Change the Control System parameter on Unit Modes screen of BACview
to MRT.