NETWORKING
AireLogic is adaptable to a variety of different network architectures and protocols. Each
controller has built-in protocol translation and can be configured for operation on
ARCnet156 or EIA-485 communication networks. See Appendix III for specific
controller specifications.
The AireLogic system can be connected to most existing building automation systems.
Some systems may require the use of special controllers and network communication
devices.
AIRELOGIC DEFAULT SETTINGS
The following is a list of AireLogic DDC controller defaults. These are the default
operating parameters set at the factory prior to shipment.
ITEM
Unit Network Address
Unit Operating Mode
Control System
DEFAULT
varies
Off
As specified
Time Clock Schedule
None
Damper Operating Mode
As specified
Fuel Selection
Heating Unoccupied Setpoint
Cooling Unoccupied Setpoint
Remote Temperature Setpoint
Heating Occupied Setpoint
Cooling Occupied Setpoint
Outside Temperature for
Heating/Cooling Changeover
Setpoint (MDT-Expert Control)
Freezestat
Heating Economizer Setpoint
Cooling Economizer Setpoint
Minimum Heating Discharge
Temperature Setpoint
Maximum Heating Discharge
Temperature Setpoint
Minimum Cooling Discharge
Temperature Setpoint
Maximum Cooling Discharge
Temperature Setpoint
Heating Discharge Setpoint
(MDT-Expert Control)
As specified
55°F
100°F
OFF
65°F
73°F
55°F
RANGE
000 – 100 rotary switches
Auto – Off – Manual
MRT (modulating room
temperature control) – MDT
(modulating discharge
temperature control)
4 Daily - 12 Holiday - 2
Override schedules
Manual – Building Pressure –
Mixed Air Temperature
Natural – Propane
40°F - 130°F
40°F - 130°F
55°F - 90°F
40°F - 130°F
40°F - 130°F
40°F - 130°F
45°F
65°F
55°F
55°F
35°F - 80°F
40°F - 130°F
40°F - 130°F
40°F - 130°F
100°F
40°F - 130°F
55°F
40°F - 130°F
75°F
40°F - 130°F
65°F
40°F - 130°F