ITEM
Cooling Discharge Setpoint
(MDT-Expert Control)
Remote Damper Position Setpoint
Mixed Air Temperature Setpoint
Building Pressure Setpoint
Manual Damper Position Setpoint
Minimum Ventilation Setpoint
Manual Damper Position Setpoint
(75/25 direct fired heaters)
Minimum Ventilation Setpoint
(75/25 direct fired heaters)
Unit Model
User PID Select
High Input Value
Low Input Value
User Control Setpoint
Maximum User Setpoint
Minimum User Setpoint
DEFAULT
73°F
RANGE
40°F - 130°F
0% Outside Air
50°F
0.00” W. C.
20% Outside Air
20% Outside Air
25% Outside Air
0% - 100%
30°F - 90°F
-0.10” - +0.10” W. C.
0% - 100%
0% - 100%
25% - 100%
25% Outside Air
25% - 100%
As specified
Direct Acting
0.00
0.00
0.00
0.00
0.00
IFL20-IFL40-IFL60-OTHER
DIRECT –REVERSE
-9999.99 – 99999.99
-9999.99 – 99999.99
-9999.99 – 99999.99
-9999.99 – 99999.99
-9999.99 – 99999.99
UNIT OPERATING MODES
There are three different modes that control the supply fan and unit operation:
 Off
 Manual
 Auto
There are also four different methods for controlling the operating modes:
 a remote control panel with one or two rotating adjustment knobs (MRT and
MDT controls)
 an intelligent room sensor and BACview panel with LCD display (MRT-Expert
controls)
 an BACview panel with LCD display (MDT-Expert controls)
 any of the these controls with an internet-based WebCTRL interface or other 3rd
party building automation system
MRT Controls:
Modulating room temperature (MRT) control is the most basic AireLogic control for
room temperature. The MRT control system includes a remote control panel equipped
with 1 or 2 potentiometers, 3 or more pilot lights, and up to 2 switches.
AireLogic units configured for MRT or MRT-Expert controls will have a fixed
discharge temperature of 70°F if the room temperature sensor is disconnected or
otherwise fails to communicate with the unit control module.
UNIT OFF MODE
Off Mode is the default unit operational mode. To place the unit in Off Mode, rotate the
“temperature setpoint” knob on the remote control panel counterclockwise to the stop.
This will place the unit in the OFF mode and extinguish the “fan on” light. The OFF
mode prevents the unit from starting.
9