Chapter 2 Description of the Equipment 2.4 Technical Data Basic Unit and Converter Module 2.4.1 Ambient Condition Temperature Operation Storage Transport Climatic Withstand Damp heat IEC 68-2-3 Climatic cycling IEC 68-2-30 Enclosure Protection Class CET 4, enclosed in panel Terminals Resistance to Vibration as per IEC 68-2-6 Resistance to Shock as per IEC 68-2-27 2.4.2 -5 to + 60 °C (23 to 140 °F) -40 to + 60 °C(-40 to 140 °F) -40 to + 85 °C (-40 to 185 °F) 40 °C (104 °F), 92 % relative humidity, 56 days 25/40 °C (77/104 °F), 21 cycles IP65 IP20 10 ... 150 Hz, 3 G 30 G, shock duration 18 ms, half a sine wave in x, y, z directions Nominal Rated Voltages Ue Primary Detection Circuit CWE 4-2.5 CWE 4-180 CWE 4-20 CWE 4-630 CWE 4-630N Motor Circuit as per IEC, SEV, VDE 0660 400 VAC 660 VAC 1 000 VAC as per CSA, UL 240 VAC 600 VAC 600 VAC Control Circuit Main relay (MR) 95. . .98, supply A1, A2 Phase sequence protection L1, L2, L3 as per IEC 947 400 VAC as per SEV 380 VAC as per UL, CSA 240 VAC Alarm relay (AL) 13/14 Auxiliary relay #1, #4, #5 as per IEC 947 400 VAC as per SEV 250 VAC as per UL, CSA 240 VAC Auxiliary relays #2, #3 50 VAC / 30 VDC Control inputs #1, #2 24 VAC/DC 2-6 Publication 825-5.025.610.910-02