APPENDICES Appendix 3 Details of Remote Buffer Memory Addresses The following shows details of remote buffer memory addresses. (1) Station-based parameter data (address: 0001H) Address CH1 Name CH2 Description Default A • Set the mode for all channels. • When a value out of the setting range is set, a moderate error (error code: 0180H) occurs. • When a value out of the setting range is set, the module operates in the automatical judgment mode. • The following shows the setting range. 0000H Mode switch setting Setting value Mode setting 0 Normal mode 9 9 Automatical judgment mode • The reflection timing of the setting value • When Initial data setting request flag (RY9) is turned off then on • To operate the module following the set value, turning off and on module power supply or remote reset is necessary. • Set the input response time of the extension input module. • The following shows the setting range. 0001H Appendix 3 Details of Remote Buffer Memory Addresses Setting value Input response time 3H 2ms Input response time 4H 5ms setting 5H 10ms 6H 20ms 7H 70ms 0005H • The reflection timing of the setting value When Initial data setting request flag (RY9) is turned off then on • When an extension I/O module is not installed, this setting is ignored. 285