PLC configuration
Configure Ethernet
Introduction
Precondition
An Ethernet bus system can be configured within the following PLC families:
l Quantum
l Atrium
l Momentum
In order to connect to the Ethernet bus system, a PCI network card must be
available in the host computer. Afterwards the Ethernet interface needs to be
parameterized and the drivers that are provided on CD need to be installed
(Configure Ethernet, p. 952 ).
After the Ethernet module has been slotted into the central backplane, the internet
address, subnet mask, gateway and frame type can be allocated by the network
administrator.
Configuration
with Quantum
33002204
The procedure for Ethernet configuration in Concept is as follows:
Step
Action
1
In the PLC Configuration window, open the Select Extensions dialog.
2
Enter the number of Ethernet modules (NOE) in the text boxes.
Response: The modules then appear in the list box in the I/O Module Selection
dialog and can be inserted into the I/O map.
3
In the PLC Configuration window, open the Ethernet I/O Scannerdialog, in
which you enter the information from the network administrator (Internet
address, subnet mask, gateway, frame type).
4
In the Online main menu, open the Connect to PLC dialog (menu command
Connect...).
5
In the Protocol Type list box, select the option TCP/IP, and in the IP address
or DNS Hostname text box, enter the address of the TCP/IP card.
6
After programming, in the Online main menu, open the Load into PLC dialog
(menu command Load...), and click on the Load command button.
Response: A message appears, asking whether you would like to start the PLC.
7
Before you confirm the message with the Yes command button, the display "link"
must appear on the Ethernet module.
141