Modbus Plus with DOS Loader
Load EXEC file
Carry out the following steps to load the EXEC file in the CPU flash RAM:
Step
CPU display
during transfer
CPU display after
transfer
Creating the
software
connection
33002204
Action
1
Select the option Load File To PLC.
Response: The Loading Process window is opened, and the warning "The
PROGRAM contents of the device being loaded could be lost after loading a new
Executive. The CONTENTS stored in the Micro H H P will always be lost after
loading a new Executive. Would you like to continue (Y/N) ? N" is displayed.
2
Acknowledge the warning with Y.
Response: The message "Node failed to enter normal mode" appears.
3
The DOWNLOAD PROGRESS window appears which shows the transfer rate.
Response: After the transfer is complete, the message "Download Operation
Successful" appears.
4
Confirm the message with RETURN.
Response: You return to the main menu.
5
Select the Exit Programoption.
Response: The DOS Loader is exited.
During transfer the CPU display is as follows:
LED
Response
Run
slow flashing
COM ACT
not lit
Modbus +
fast flashing
After transfer the CPU display is as follows:
LED
Response
Run
not lit
COM ACT
not lit
Modbus +
fast flashing
Carry out the steps given in chapter Creating a Project, p. 75.
Note: If you recieve an error message, close Concept and start the
BDRESET.EXE file (in the \Concept directory) to reset the SA85. Then start again
from the first step.