Download EEGS - HKFEMC
Transcript
(viii) The tank shall be fitted with an approved content gauge unit. Provide an accurate measuring device for the calibration of the content gauge and a supporting stand which shall be fabricated form angle iron complete with strut and tie members as may be deemed necessary. They shall be designed in such a way that it will be possible to remove the tank without first lifting it. A mild steel oil drip tray welded to the angle bracket or stand shall also be included. Exact height of the frame shall be determined to suit site requirement. (c) Painting of the Daily Service Fuel Tank All parts of the exterior surfaces of the tank shall be thoroughly cleaned by mechanical means to remove all rust, mill scale, grease and other foreign matters to achieve a bright, rust free and dry surface and then painted with one coat of zinc rich primer, one coat of epoxy based under coat and two finishing coats of approved paint. The interior surface of the tank shall be thoroughly dried out and applied with a thick coat of linseed oil to prevent rusting. C12.7.3 Fuel Transfer Pumping System (a) Electrical Fuel Transfer Pumps Rotary fuel transfer pumps complete with all necessary accessories including strainers, check valves, gate valves etc. shall be provided. (i) The pumps shall be positive displacement type, with high quality cast iron body, high tensile steel shafts and built in internal relief valve. (ii) Each pump shall be capable of delivering 'ultra low sulphur' diesel fuel oil at 300 kPa 950 rpm maximum with capacity. For each pair of pumps a manual switch shall be provided to select the pump running mode as "duty" or "standby" respectively. (iii) The coupling motor shall be flame proof 3 phase, 50 Hz, 380V with no volt release and overload protection. It shall have a manual/auto/off switch with connections for remote start/stop operation by the level switch at the daily service tank. The duty pump shall be actuated when the fuel level in the daily service tank fall below 30% of the tank capacity, cut off automatically when the tank is 90% full. The pumps shall also be inoperative when the fuel level in the underground storage tank falls below a pre-set level. Section C12 Page 19 of 31 EE_GS 2012 Edition