B9.5.4
B9.5.5
B9.6
B9.7
Cables Boxes
(a)
Cable boxes shall be suitable for terminating the cables directly
into the switchgear.
(b)
Where cable boxes are used for three-core cables, the sweating
sockets on the two outer phases shall be so fixed to incline
towards the centre to minimise bending of the cable cores.
Where there is more than one core per phase, the socket block
shall be so fixed as to minimise bending of the cable cores, and
spacer clips shall be used.
Labels and Warning Notice
(a)
Labels shall be fixed by screws on the non-detachable parts of
the panel at a height of 1350 mm or above.
(b)
'Danger - H.V. Live Terminals/ 危 險 – 高 壓 帶 電 電 極 '
warning labels shall be attached to the access covers of the air
insulated cable boxes, CT chambers and busbar, and shall be
colored red with white lettering in both English & Chinese
characters.
(c)
In addition to automatic screening shutters and barriers,
warning labels shall also be provided for all live parts, such as
test terminal blocks.
HIGH VOLTAGE AUTO-TRANSFORMERS
B9.6.1
The auto-transformers shall be mounted firmly on to the concrete
floor finished to the standard requirements as recommended by the
equipment manufacturer. The floor construction shall be designed to
withstand the operating weight of the auto-transformers.
B9.6.2
The installation shall be carried out in strict accordance with the
recommendations so as to keep the noise and vibration generated by
the auto-transformers to the minimum.
HIGH VOLTAGE POWER FACTOR CORRECTION CAPACITORS
B9.7.1
Positioning of the power factor correction capacitors shall be done
by means of the built-in combined jacking and haulage lugs.
B9.7.2
The installation shall strictly follow the equipment manufacturer‟s
recommendations.
Section B9
Page 5 of 6
EE_GS
2012 Edition