18. Component Specifications
Power Supplies
Mains and batteries must be connected to the CCU-16 and each SCU-16. Mains must be permanently
connected and local wiring regulations must be followed. No other power connections are required.
External cabling
Outstation lines
2-core 1.0 mm2 or 1.5 mm2 enhanced fire-rated cable, up to 1 km per line.
CCU to SCU, SCU to SCU
Two 4-core 1.0 mm2 or 1.5 mm2 enhanced fire-rated, max 800 metres between CCU and last SCU.
Max 200 metres between individual units.
ECU to CCU
Two 4-core 1.0 mm2 or 1.5 mm2 enhanced fire-rated cable, up to 200 metres. Do not use a larger
multicore as audio and data must be separately screened.
CCU-16 Master control unit and SCU-16 Slave control unit
Base dimensions
412 mm W x 250 mm H x 80 mm D
Lid dimensions
435 mm W x 269 mm H x 11 mm D
Weight,
unpacked 3.1 Kg, packed 4.0 Kg
Power supply
Mains supply
230 VAC 50/60 Hz
Internal supply
27.6 VDC
Output current
1 amp max
Supply monitored for failure
Yes
Batteries monitored for failure
Yes
Quiescent current
<30 mA
Max current
< 50 mA
Fuses
Mains fuse
1 A (T) 20 mm HRC
Battery fuse
1 A (F) 20 mm
Batteries, per CCU-16 and SCU-16
Two 12 Volt 7 Ah
Each CCU & SCU needs a separate mains supply
Line specification
Max Number of lines per CCU / SCU-16 16
Number of outstations per line
1
Lines monitored for open circuit
Yes
Lines monitored for short circuit
Yes
Lines monitored for earth fault
Yes
SigTEL
Emergency Voice
Communication System
Approved Document No. DCP0001483 Rev 3
Page 29 of 32