Download - Show more
Transcript
Saia-Burgess Controls AG Function Communication - Connect Sbus 252. - Write Register 110 - new station number. - Write Register 60 - 0. 3 Automatic configuration The compact room controllers can be configured automatically via the Config and Room FBoxes. After every restart, a flag is passed to the Room FBox to tell it that the controller has been restarted. The FBox then checks that the configuration matches the associated Config FBox. If this is not the case, all the control parameters are copied over automatically from the Config FBox to the compact room controller. This option reduces commissioning to the address-setting operation. This means that after a device replacement in the course of support work, functionality can be reliably restored by the Saia PCD® alone. See also the description of the individual functions in the following sections. Manual for PCD7.L79xN room controllers │ Document 27 / 602 EN02 │ 2013-08-20 3-3