ectin Terminate the five wires to the appropriate terminals on the power terminal block, using the M5 hex-head screws provided. Recommended tightening torque 2Nm. The colour code i s L f - 13 brown, Neutral light blue, Earth green/yellow. Form the five wires into a loom. Route the three phase wires around the top of the power assembly (see diagram) to the bottom of the circuit breakers. Trim to length and terminate to the inlet terminals of each group of circuit breakers, in sequence (from the left): - Recommended tightening torque 2Nm. Trim to length and terminate the earth wire into the left position of the earth bar, entering from below. Use the bootlace ferrule provided to protect the stranded cable and ensure good earth contact. Recommended tightening torque 2Nm. Trim to length and terminate the neutral wire into the DIN terminal to the left of the circuit breakers. Recommended tightening torque 1.2Nm. Note: routing the phase wires past the neutral terminal ensures that, should it be necessary to retrofit an RCD to the power assembly later on, this may be easily done. .9.5. The power assembly signal looms Until the front door is fitted, there is no point in running in the power assembly signal looms. See 4.10.2 below.