Please note the following maximum cable sizes: Earth and Neutral bars: 2 . 5 k W Phase terminals: 5kW Phase terminals: 10kW Phase terminals: 10 x 10mm2, 3 x 16mm2 4mm2 6mm2 3 5m m2 It is occasionally necessary to use larger cable sizes on the 2.5kW and 5kW dimmers, and an adapter kit is available, with 10mm2 and 16mm2 DIN terminals for oversized cables. See section 10.7 for part numbers. Note that bootlace ferrules are required to be fitted to the earth and neutral wires if stranded cable is used. a) Terminate load earth wires into the earth busbar on the left side of the power assembly. Recommended tightening torque 1.5Nm (2.5mm2 cable) to 2 N m (10mm2 cable). Terminating load wiring. Note hat numbering is always from left to right, ie: E a h 1-12, Neutml I-12, Phase 1- 12. f i e same rule applies to 3x 1Ok W and 6xSkW Power Assemblies. Tip: It's easier to fit the bottom Power Assembly first, terminate the load wirin5 then fit the middle Power sembly, and so on. page 23