Download ComBricks User Manual - Streamline Process Management
Transcript
COMbricks – User Manual 10.5 DP/DP coupling or Gateway mode A unique feature of the PBS-001 is that it can be used as a DP/DP coupler for up to 10 networks, where each network can have different bus parameters and baud rates. It connects the networks on an I/O level, where you can decide how many bytes need to be transferred. For each network a PBS-001 is needed. So if you wish to connect 2 networks, you need 2 PBS-001 modules in one COMbricks set. A typical COMbricks configuration for a DP/DP setup may look like Fig. 64: Fig. 64 - COMbricks configuration screenshot of the web server Fig. 65 - Schematic representation of the gateway Slot 1 belongs to Network 1. Slot 2 is connected to Network 2. These networks can now be coupled via the configuration tools of each master. For example, if you want to transfer 4 bytes, the setup for the configuration tool of network 1 will look as follows: Fig. 66 - Configuration for Network 1 The first slot is used for the PBS-001 module. The next slot is used for anther PBS-001 module, but a gateway module must be selected because the PBS-001 itself does not have any I/O. _______________________________________________ Version 5.4.0 – June 2014 COMbricks-User-Manual1-EN.docx Page 103 / 184 © PROCENTEC 2014 - Copyright - all rights reserved