104 VAV Terminal Control Applications Application Note Group Para(Cont.) meter Point Default Location Value Cold Deck Damper Control (Cont.) Cold Dk BD 236 0.0 Override Disable Constant Volume Linked Dampers Single Duct Conversion Indep Cold Deck w/ Dependent Hot Deck Pressure Indep Constant Volume Separate Dampers Damper Control Damper Control Damper Control Cold Dk Preset ADF 236 0.0 cfm Damper Control Damper Control Damper Control Cold Dk Prop Band ADF 191 -1600 cfm Damper Control Damper Control Damper Control Cold Dk Setpt AO 8 0.0 cfm Damper Control Damper Control Damper Control 500.0 cfm Used Used Cold Deck Flow Setpts Occ CD ADF 144 Clg Max Occ CD Clg Min ADF 143 100.0 cfm Used Used Occ CD Htg Min ADF 145 0.0 cfm Used Used Unocc CD Clg Max ADF 149 400.0 cfm Used Used Unocc CD Clg Min ADF 148 100.0 cfm Used Used Unocc CD Htg Min ADF 150 0.0 cfm Used Used Constant Volume Setpts Occupied ADF 143 Flow Setpt 400.0 cfm Used Used Unoccupied Flow Setpt ADF 144 200.0 cfm Used Used Warmup Flow Setpt ADF 145 400.0 cfm Used Used Calculated DAR DAR Discharge Set Points Actual ADF 36 Disch Setpt Low Disch Setpoint ADF 172 55.0*F DAR DAR Disch Reset Band ADF 139 60.0*F DAR DAR Disch Air Deadband ADF 194 2.0*F DAR DAR DA ADF 200 Temperature Tuning 0.025 DAR DAR Actual Disch Flow Setpt 0.0 cfm DAR DAR ADF 25 Continued on next page . . .