Download VAV Terminal Control Applications Application Note
Transcript
VAV Terminal Controller Applications Application Note 3 Key Concepts Variable Air Volume (VAV) Controller The Variable Air Volume (VAV) controller is an electronic device for digital control of single duct, dual duct, fan powered, and supply/exhaust VAV terminal configurations. Along with the control capability of the VAV box, the controller can also integrate the control of the room or zone baseboard heat and lighting logic. You may use the VAV as a standalone controller or connected to the Metasys® Network through a Network Control Module (NCM), Metasys Companion™/Facilitator™, or N30 Supervisory Controller. When connected to the Metasys Network, the VAV provides all point and control information to the rest of the network. The devices communicate through the N2 Bus. HVAC PRO™ Release 6.00 or later allows you to configure the Variable Air Volume controller with more ease, simplicity, and application flexibility than ever before. Refer to the Getting Started on HVAC PRO chapter of the User’s Guide to HVAC PRO (LIT-6375040) for information on using the windows environment, general information pertaining to starting HVAC PRO, and hardware/software requirements. HVAC PRO Release 6.00 or later allows a VAV controller application to be downloaded with one sideloop. A sideloop is a control loop where an input controls an unused output, in addition to the VAV controller’s main strategy. For example, you may want to control a humidifier based on return air humidity. Since the VAV controller does not offer a humidity loop, a sideloop could accomplish this task. This sideloop strategy could provide an occupied setpoint and an optional unoccupied setpoint. Moreover, you could disable the output (either from the On status of the controller’s Shutdown mode or the Off status of a binary input interlock) in order to prevent the humidifier from operating when no air is flowing through the VAV box. If more than one sideloop is required, HVAC PRO Release 5.10 or later allows downloading of a VAV terminal control configuration to a UNT11n-1. The VAV controller cannot be downloaded as a point multiplexer. The unused points, however, can be user defined and used with a single sideloop. For more detailed information on the operation of sideloops, see Appendix A: Sideloop Applications (LIT-6375160).