Transcript
108 VAV Terminal Control Applications Application Note Constant Volume Linked Dampers Single Duct Conversion Indep Cold Deck w/ Dependent Hot Deck Group Para(Cont.) meter Point Default Location Value Pressure Indep Constant Volume Separate Dampers Modes (Cont.) Occ Stop Time ADI 226 00:00 Hr:Mn Occupied Mode Occupied Mode Occupied Mode Occupied Mode Occupied Mode Occupied Command BD 227 1 On Occupied Mode Occupied Mode Occupied Mode Occupied Mode Occupied Mode Occupied Status BD 22 0 Unocc Always Always Always Always Always Restart Delay ADF 184 1.0 Minute Power Fail Restart Power Fail Restart Power Fail Restart Power Fail Restart Power Fail Restart Restart Status BD 21 0 Off Power Fail Restart Power Fail Restart Power Fail Restart Power Fail Restart Power Fail Restart Shutdn Box BD 230 Close Command 0 Off Shutdown Shutdown Shutdown Shutdown Shutdown Shutdn Box BD 229 Open Command 0 Off Shutdown Shutdown Shutdown Shutdown Shutdown Shutdown Status BD 23 0 Off Shutdown Shutdown Shutdown Shutdown Shutdown Standby Command BD 228 0 Off Standby Standby Standby Standby Standby Temp Occ Status BD 14 0 Off Temporary Occupied Mode Temporary Occupied Mode Temporary Occupied Mode Temporary Occupied Mode Temporary Occupied Mode Warmup Command BD 225 0 Off Always Always Always Always Always Occupied Damper Setpts Occ Bbd ADF 147 Min 0.0 cfm Used Occ Clg Max ADF 144 500.0 cfm Used Occ Clg Min ADF 143 100.0 cfm Used Occ Htg Max ADF 146 100.0 cfm Used Occ Htg Min ADF 145 100.0 cfm Used Continued on next page . . .