Download VAV Terminal Control Applications Application Note

Transcript
VAV Terminal Controller Applications Application Note
Group Para(Cont.) meter
Point
Default
Location Value
Hot Deck Flow Setpts
Occ HD
ADF 179
Clg Min
Pressure
Indep
0.0 cfm
Used
Constant
Volume Separate
Dampers
107
Constant
Volume Linked
Dampers
Single
Duct
Conversion
Indep
Cold
Deck w/
Dependent
Hot Deck
Occ HD
Htg Max
ADF 177
500.0
cfm
Used
Occ HD
Htg Min
ADF 176
100 cfm
Used
Unocc HD
Clg Min
ADF 183
0.0 cfm
Used
Unocc HD
Htg Max
ADF 181
300.0
cfm
Used
Unocc HD
Htg Min
ADF 180
100.0
cfm
Used
Wrmup HD
Clg Min
ADF 153
0.0 cfm
Used
Wrmup HD
Htg Max
ADF 156
500.0
cfm
Used
Wrmup HD
Htg Min
ADF 155
100.0
cfm
Used
1.0 °F
Discharge
Air Low
Limit
Discharge
Air Low
Limit
200
Discharge
Air Low
Limit
Discharge
Air Low
Limit
Dis Air Low ADF 172
Limit
58.0°F
Discharge
Air Low
Limit
Discharge
Air Low
Limit
Dis Air
Prop Band
ADF 173
-3.0°F
Discharge
Air Low
Limit
Discharge
Air Low
Limit
Boost Ovrd ADF 175
Time
30.0
Minute
Boost
Mode
Boost
Mode
Boost
Mode
Boost
Mode
Boost
Mode
Boost
Status
BD 15
0 Off
Boost
Mode
Boost
Mode
Boost
Mode
Boost
Mode
Boost
Mode
Occ Ovrd
Time
ADF 174
30.0
Minute
Temporary
Occupied
Mode
Temporary
Occupied
Mode
Temporary
Occupied
Mode
Temporary
Occupied
Mode
Temporary
Occupied
Mode
Occ Start
Time
ADI 225
00:00
Hr:Mn
Occupied
Mode
Occupied
Mode
Occupied
Mode
Occupied
Mode
Occupied
Mode
Low Limit Setpoints
Dis Air
ADF 194
Deadband
Dis Air
Integ Time
ADF 193
Modes
Continued on next page . . .