Transcript
114 VAV Terminal Control Applications Application Note Constant Volume Linked Dampers Single Duct Conversion Indep Cold Deck w/ Dependent Hot Deck Group Para(Cont.) meter Point Default Location Value Zone Set Points Actual Zone Setpt ADF 21 Calculated Disch Air Reset Only DAR Actual Zone Bias ADF 20 Calculated DAR DAR Zone Prop Band ADF 132 10.0 DAR DAR Zone Integ Time ADF 133 500 Ticks DAR DAR Zone Dead-band ADF 146 0.0*F DAR DAR Occ Bias ADF 134 2.0°F Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Occ Setpt ADF 129 70.0°F Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Stby Bias ADF 135 4.0°F Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Stby Setpt ADF 130 70.0°F Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Unocc Bias ADF 136 9.0°F Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Unocc Setpt 71.0°F Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt Single Zone Setpt ADF 131 Zone Temp Damper Config Zone Dmp ADF 161 Deadbd Zone Dmp Stroke Time ADF 160 Zone Temp Damper Control Zone Tmp AO 7 Dmp Cmd Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 Pressure Indep Constant Volume Separate Dampers 5.0% Used 2.0 Minute Used 0.0% Used www.johnsoncontrols.com Published in U.S.A.