Download User`s Manual - CTi Automation
Transcript
CHAPTER 3 - INSTALLATION AND CONNECTION 3.2.1 Power and Grounding Terminals Description of the Power Terminals: L/L1, N/L2, L3: AC power supply. U, V and W: Motor connection. PE: Grounding connection. BR: Connection terminal for the braking resistor. Not available for 1.6 A, 2.6 A and 4 A/200-240 V and 1.6 A and 2.6 A/110-127 V and 7.3 A/200-240 V three-phase models. +UD: Positive connection terminal (DC Link). This terminal is used to connect the braking resistor (connect also the BR terminal). Not available for 1.6 A, 2.6 A and 4.0 A/200-240 V and 1.6 A and 2.6 A/ 110-127 V and 7.3 A/200-240 V three-phase models. a) Models 1.6 A, 2.6 Aand 4.0 A/200-240 V and 1.6A and 2.6 A/110-127 V (single-phase) L/L1 N/L2 U V W PE b) Models 7.3 A and 10 A/200-240 V and 4.0 A/110-127 V (single-phase) L/L1 N/L2 BR + UD U V W PE c) Models 1.6 A, 2.6 A, 4.0 A, 7.3 A/200-240 V (three-phase) d) Models 10.0 A and 15.2 A/200-240 V (three-phase) Figure 3.4 a) b) c) d) - CFW-10 Power Terminals Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected] 27