CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
2) Automatic Operation: open the DI and make the dynamic setting of
the PID regulator, i.e., set the proportional gain (P520), integral
gain (P521) and differential gain (P522).
NOTE!
The inverter setting must be correct in order to obtain a good
performance of the PID regulator. Ensure the following settings:
Torque boosts (P136 and P137) and slip compensation (P138) in
the V/F mode control (P202 = 0 or 1);
Acceleration and deceleration ramps (P100 to P103);
Current limitation (P169).
Input via terminals 6 and 7
4-20 mA
Pressure
Transducer
0-25 bar
CFW-10
The set point can be
changed through keys or
potentiometer according to
P221/P222
L/L1 N/I2 U
AI1 - Feedback
DI3-Manual/Auto
DI4-Run/Stop
1 2 3 4 5 6 7 8 9 10111 2
DI1 Gen. enable
P525
Content
V
Process
W PE
X1
Line
Inverter parameterization:
P203 = 1
P221 = 0 or 3
P222 = 0 or 3
P229 = 1
P234 = 100
P235 = 1
P236 = 000
P238 = 100
P240 = 0
P265 = 27
P525 = 0
P526 = 0.1
P527 = 0
P528 = 25
Figure 6.24 - Application example of an inverter with PID regulator