Download PROFIBUS-DP Interface Module User`s Manual
Transcript
5 PROCEDURES BEFORE SYSTEM OPERATION MELSEC-Q 5. PROCEDURES BEFORE SYSTEM OPERATION 5.1 Procedures before Operation The procedure for newly connecting QJ71PB92D to an existing PROFIBUS-DP network is explained below. For the operation of GX Configurator-DP, refer to the PROFIBUS-DP configuration operating manual. Start Set the CPU module to STOP. Refer to Section 5.4. Start the self-diagnosis of the QJ71PB92D. Is the self-diagnosis result normal? (Are the TEST and FAULT LEDs off?) No This is a hardware fault. Confirm the self-diagnosis result and consult your local Mitsubishi representative. Yes Set the parameters using GX Configurator-DP. 5 Refer to Section 5.1.1. No Is the automatic refresh setting used? Yes Reset the CPU module. Is the QJ71PB92D placed in the mode that enables exchange with slave stations? (Is the operation mode set to MODE 0 or MODE E?) No Change the mode of the QJ71PB92D to the mode that enables exchange with slave stations (MODE 0 or MODE E). 1 Yes Connect the PROFIBUS cable to the slave station, and start the slave station. Start the QJ71PB92D communications. Has the QJ71PB92D started normal communications? (Are the READY and TOKEN LEDs on and the PRM SET and FAULT LEDs off?) Refer to the manual of the slave station. 2 No (Recheck the parameter settings.) Yes Ready 1: Change the operation mode in either of the following methods. Change from GX Configurator-DP. Use the operation mode change request area (buffer memory address: 2255) and operation mode change request signal (Y11). 2: Start the communications in either of the following methods. Turn on the exchange start request signal (Y00). Start from GX Configurator-DP. 5-1 5-1