Download SD17060E - Advanced Micro Controls Inc
Transcript
8 CONFIGURATION MODE DATA FORMAT Input Data Format The correct format for the Network Input Data when the SD17060E is in Configuration Mode is shown below. EtherNet/IP Word Modbus/TCP Register Configuration Data 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 Control Word Mirror of Output Data Config Word Mirror of Starting Speed: Upper Word Mirror of Starting Speed: Lower Word Mirror of Motor Steps/Turn Mirror of Hybrid Control Gain Mirror of Encoder Pulses/Turn Mirror of Idle Current Percentage Mirror of Motor Current (X10) Mirror of Current Loop Gain Table 8.4 Network Input Data Format: Configuration Mode Control Word Format (Word 0) When the Configuration data is valid and accepted, this word mirrors the value of the Control Word written to the SD17060E. When the SD17060E is not configured, or the data written to it is invalid, then this word has the same format of Status Word 1 when the SD17060E is in Command Mode. This format is explained in the Status Word 1 Format section starting on page 88. On power up, the value of this word will be 6408h. When in Configuration Mode, bit 13 of word 0 is set to “1” when stall detection is enabled. When in Command Mode, bit 13 of word 0 is set to “1” when there is a configuration error. When using the state of bit 13 of word 0 in your logic, always include the state of bit 15 of word 0 to assure that you are only acting on the bit when in the proper mode. Invalid Configurations The following configurations are invalid: 1) Setting any of the reserved bits in the configuration words. 2) Setting any parameter to a value outside of its valid range. This includes setting the Lower Word of the Starting Speed to a value greater than 999. 3) You configure two or more inputs to have the same function, such as two CW Limit Switches. 4) You configure the SD17060E to use an encoder, but you do not configure Inputs 1 and 2 as Quadrature Encoder Inputs. 5) You configure the SD17060E to use an encoder, but you do not set the Encoder Pulses/Turn value in word 6. 6) Setting the Stall Detection Enable Bit without configuring the SD17060E to use an encoder. 74 ADVANCED MICRO CONTROLS INC.