110 18 18-7 LIST OF PARAMETERS Control Output Screen Group (group 6) Display Symbol Description of Function Initial Value Setting Range Lock OUT1 ACT Output 1 control characteristics Reverse: Reverse characteristics Direct: Direct characteristics Reverse 1 RST Output preset value at output 1 reset 0.0 to 100.0 % 0.0 % 1 ERR Output preset value at output 1 error 0.0 to 100.0 % 0.0 % 1 CYC Output 1 proportional 1 to 120 s cycle time Contact (Y) : 30 s 1 SSR (P) : 3 s OUT2 ACT *1 Output 2 control characteristics Reverse: Reverse characteristics Direct: Direct characteristics Direct 1 RST *1 Output preset value at output 2 reset 0.0 to 100.0 % 0.0 % 1 ERR *1 Output preset value at output 2 error 0.0 to 100.0 % 0.0 % 1 CYC *1 Output 2 proportional 1 to 120 s cycle time Contact (Y) : 30 s 1 SSR (P) : 3 s Output 1 rate-of-change limiter OFF, 0.1 to 100.0 %/s OFF 1 Output 2 rate-of-change limiter OFF, 0.1 to 100.0 %/s OFF 1 Rate Limiter Out1 Out2 *1 *1 Control output 2 is optional and is not displayed when it is not installed.