F000
F001
Direct Access Parameter Information
The HX7 ASD has the ability to allow the user direct access to the motor control functions. The functions
listed below have an associated Parameter Number which accesses its setting. There are two ways in
which the motor-control parameters may be accessed for modification: Program ⇒ applicable menu path
or Program ⇒ Direct Access ⇒ applicable parameter number. Both methods access the parameter via
the Program mode. Once accessed, the parameter may be viewed or changed.
The Program mode allows the user to develop an application-specific motor control profile. Motor
control functions may be set to accommodate specific power and timing requirements for a given
application. The configurable parameters of the Program mode that have user-accessible Parameter
Numbers are listed and described below.
Note:The setup procedures included within this section may require a Reset before performing the procedure.
Application-specific settings may then be performed. The pre-Reset conditions may be saved (see F007).
Direct Access Parameters/Numbers
Automatic Accel/Decel #1
Direct Access Number — F000
Program ⇒ Fundamental Parameters
Parameter Type — Check Box
Factory Default — Disabled
This parameter Enables/Disables the ability of the ASD to adjust the
acceleration and deceleration rates in accordance with the applied load
automatically.
Changeable During Run — No
The adjusted acceleration and deceleration times range from 12.5% to 800% of
the programmed values for Acceleration Time #1 (F009) and Deceleration
Time #1 (F010).
Settings:
0 — Manual
1 — Automatic ACC/DEC
2 — Automatic ACC Only
Note:
The motor and the load must be connected prior to selecting
Automatic Accel/Decel.
Automatic Torque Boost
Direct Access Number — F001
Program ⇒ Fundamental ⇒ Motor Set #1
Parameter Type — Selection List
This parameter allows the ASD to adjust the output torque in accordance with
the applied load automatically. When enabled Autotuning is performed — the
motor should be connected before performing an Autotune.
Factory Default — Disabled
Changeable During Run — No
Settings:
0 — Disabled
1 — Automatic Torque Boost + Autotuning
2 — Sensorless Vector Control + Autotuning
HX7 ASD Programming and Operation Manual
45