Download HX7 Adjustable Speed Drive Programming and
Transcript
F000 F001 Direct Access Parameter Information The HX7 ASD has the ability to allow the user direct access to the motor control functions. The functions listed below have an associated Parameter Number which accesses its setting. There are two ways in which the motor-control parameters may be accessed for modification: Program ⇒ applicable menu path or Program ⇒ Direct Access ⇒ applicable parameter number. Both methods access the parameter via the Program mode. Once accessed, the parameter may be viewed or changed. The Program mode allows the user to develop an application-specific motor control profile. Motor control functions may be set to accommodate specific power and timing requirements for a given application. The configurable parameters of the Program mode that have user-accessible Parameter Numbers are listed and described below. Note:The setup procedures included within this section may require a Reset before performing the procedure. Application-specific settings may then be performed. The pre-Reset conditions may be saved (see F007). Direct Access Parameters/Numbers Automatic Accel/Decel #1 Direct Access Number — F000 Program ⇒ Fundamental Parameters Parameter Type — Check Box Factory Default — Disabled This parameter Enables/Disables the ability of the ASD to adjust the acceleration and deceleration rates in accordance with the applied load automatically. Changeable During Run — No The adjusted acceleration and deceleration times range from 12.5% to 800% of the programmed values for Acceleration Time #1 (F009) and Deceleration Time #1 (F010). Settings: 0 — Manual 1 — Automatic ACC/DEC 2 — Automatic ACC Only Note: The motor and the load must be connected prior to selecting Automatic Accel/Decel. Automatic Torque Boost Direct Access Number — F001 Program ⇒ Fundamental ⇒ Motor Set #1 Parameter Type — Selection List This parameter allows the ASD to adjust the output torque in accordance with the applied load automatically. When enabled Autotuning is performed — the motor should be connected before performing an Autotune. Factory Default — Disabled Changeable During Run — No Settings: 0 — Disabled 1 — Automatic Torque Boost + Autotuning 2 — Sensorless Vector Control + Autotuning HX7 ASD Programming and Operation Manual 45