Download SIMADYN D Digital Control System Processor module PT20
Transcript
Technical data 5. Technical data 5.1. GENERAL INFORMATION INSULATION GROUP V DC AMBIENT TEMPERATURE STORAGE TEMPERATURE HUMIDITY CLASS ALTITUDE RATING MECHANICAL STRESSING PACKAGING SYSTEM DIMENSIONS BOARD WIDTH WEIGHT CURRENT DRAIN A acc. to VDE 0110 Para. 13 Group 2 at 24 V DC, 15 V DC, 5 0 to +55 degrees C with natural air cooling -40 to + 70 degrees C F acc.to DIN 40040 S acc. to DIN 40040 Mounted in stationary equipment which is not necessarily vibration-free ES 902 C 233.4 * 220 mm 2 slots, 40.28mm 1.0 kg P5 2.1 A P15 110 mA + encoder load N15 130 mA VCRAM 0.5 mA P24 0.1 A + load, binary outputs 5.2. BINARY INPUTS No. INPUT VOLTAGE for 0 signal for 1 signal Input current for 1 signal Delay time 24 , non-floating, interrupt-capable +24 V rated voltage -1 V to +6 V or open-circuit binary inputs +13 V to +33 V approx. 5 mA 500 usec. 5.3. BINARY OUTPUTS No. POWER SUPPLY VOLTAGE -RATED VALUE -RIPPLE -PERMISSIBLE RANGE -BRIEFLY OUTPUT CURRENT FOR 1 SIGNAL -RATED VALUE -PERMISSIBLE RANGE SHORT-CIRCUIT PROTECTION LIMITING INDUCTIVE TURN-OFF VOLTAGES TOTAL LOAD RESIDUAL CURRENT SIGNAL LEVEL -AT 0 SIGNAL -AT 1 SIGNAL Switching delay 6 16, non-floating External 24 V DC 3.6 V -DC + 20 to + 30 V incl. ripple + 35 V less than 0.5 sec.. 50 mA 0.2mA to 50 mA electronic to Vcc+ 1V 80% at 50 degrees C, all outputs, 50 mA 20 uA at 0 signal max. 3V min. supply, - 2.5V max. 15 usec. Edition 04.97 Siemens AG Dk-Nr. 224641 SIMADYN D Hardware User Manual