Overview The ILC Apprentice II lighting controller is a microprocessor-based, programmable lighting controller capable of advanced lighting control in a master-slave application. It is an economical controller that can link up to 48 control points and has the capability of using hardwired or LightSync™ data line switches. You can program the switch inputs to control any or all of the relay outputs. The controller features ILC Softcross™ relays with true zero-cross switching. This User Guide outlines the capabilities of the controller and its add on modules. The ILC Apprentice II is UL and FCC approved for commercial applications. Structure The major components making up the controller are: • enclosure • control transformer • CPU board with integral keypad/display • Input board(s) • Output board(s) • lighting relays Enclosure – The enclosure is rated NEMA 1. It contains a line voltage section for the control transformers and lighting relays and a low voltage section. Enclosures are available in 4 sizes to accommodate 4, 8, 16, or 32 relays. Transformer – A 40 VA multi-tap control transformer, 120/277 VAC or optional 120/347 VAC that provides the 24 VAC input to power the controller electronics and input/output board(s). CPU Board – The CPU board provides the controller’s intelligence and memory. Major components include: • Keypad/display – 4-line LCD display and six durable, comfortable push buttons. • Power Supply – converts the 24 VAC input to the +5, -5 and +12 VDC required by the controller logic and communications circuits. A power switch provides the means of energizing/de-energizing all controller electronics. • Communications – USB port, add-on card expansion socket. • Override Switches – push button override switches turn relays all ON or all OFF. Version 2B 6/16/14 ILC Apprentice II User Manual • Microprocessor – executes the computer code and coordinates all controller functions including the controller real time clock. • Flash Memory – contains the controller operating system and basic tasks. • the EEProm memory– store the user-entered operating parameters. • Real time clock – maintains time and date for up to 30 days without power. Input Board(s) – Each input board provides four (4) switch inputs. Major components include: • Switch Inputs – can accept input from either 2- or 3-wire momentary or maintained dry contact devices. Each switch input features a switch pilot LED output, which can be programmed to track the state of a single relay, relay group or preset. The inputs are optically isolated, noise- and surge-resistant. A switch and pilot may be located up to 1500 feet from the controller, provided you use a minimum of 18 gauge wire. Output Board(s) – Each output board provides four (4) relay outputs. Major components include: • Relay Outputs – Each optically isolated output switches its associated lighting relay ON and OFF. Each output has an associated LED. The LED lights when the output switches the relay ON. • Relay – SoftCross™ Relay: Electrically held N.O or N.C. lighting relay rated for up to 277 VAC @ 20 full load amps. 1-Pole Relay Option: Single-pole relay capable of controlling lighting loads up to 347VAC @ 20 full load amps. 2-Pole Relay Option: Two-pole relay capable of controlling lighting loads up to 277VAC @ 20 full load amps per pole.