Download GE SECURITY EMEA BVBA
Transcript
DET NORSKE VERITAS Report No: 2005-3246, rev. 01 TECHNICAL REPORT Table 29 – Generation of tamper during incorrect authorization codes Test results for “unset mode” Step General measurement and Measurement result criteria 2 Still unset User input disabled, user tamper recorded in the event log. Notification output for “keypad tamper” activated 3 After 120 seconds System unset “user tamper” acknowledged Indications restored Clause 12.6.4 Requirement - test Setting procedures Result Pass/fail P P Verdict a) Object of the test b) Principle 8.2.3 Table 30 - Tests of setting procedures - Test results Step General measurement and Measurement result criteria 1 8.10 OK Table 4 OK “Fails to set” indication OK Fails to set OK (Zone 2) 8.2.3 OK 2 Zone 2 omitted IAS set Table 4 OK Indication < 180 seconds OK 3 Tamper Zone 1 “Fails to set” indication OK Fails to set OK Table 4 OK 4 Zone 1 overridden/bypassed IAS set Table 5 OK IAS restored 5 Hold-up Zone 3 “Fails to set” indication OK Fails to set OK Pass/fail P P P P P Page 46 Reference to part of this report which may lead to misinterpretation is not permissible. 2005-3246 final.doc