TAC 200 OTP Handbook
Special functions, P:16–
4 Special functions, P:16–
4.1 List of available functions
The functions P:16–P:66 are normally only used during commissioning or if
special adjustments are required.Normally it is sufficient to use P:00–P:15 and
for this reason the display scrolls through P:15–P:00, or vice versa.
To access functions P:16 and higher:
1.
Simultaneously press
2.
Press
P
or
P
P
and
P
to get to P:16.
to step up or down within the new interval. To return
to P:00–P:15, either press P and P simultaneously, or wait for
approximately two minutes for the controller to return to P:00
automatically.
These are the functions P:16–P:66:
P:
Meaning
P:16 Max. supply water temperature
P:17 Min. supply water temperature
}
P:18
P:19
P:20
P:21
P:22
x(1)
y(0)
Reset curve
y(1)
dimension points
y(2)
Start time curve adjustment
P:23
P:24
P:25
P:26
P:27
Start time low
Start time high
Max. holiday compensation adjustment
Max. start time (h)
Optimisation tolerance (°C)
P:29
P:30
P:31
P:32
Room sensor authority
Room I time (minutes)
Room dead band (°C)
Min./Max. room influence (°C)
P:34
P:35
P:36
P:37
Supply P band (°C)
Supply I time (minutes)
Running time actuator (s)
°C×min at on/off
P:38 Morning boost time (minutes)
P:39 Morning boost (°C)
TAC AB, Feb 200
4:1