8-10
Inspection and Protection Functions
Confirmation before Requesting for A/S
In the event an error occurs in servo alarm that is not displayed, it describes
the cause and action.
If the main circuit power is allowed in a cause investigation, it is dangerous.
After the power shall be disconnected to completely turn out the
discharge-confirming lamp, take action on it. In the event the error is not
resolved after taking an action, promptly request for A/S to the company.
The chart below shows the diagnosis on errors when the alarm does not occur.
Table 8.5 Diagnosis on errors when the alarm does not occur
Errors
Cause
Inspection and Action
The motor does not run.
The power is not inputted.
Make correction after confirming the power
wiring.
Motor and encoder wiring is erroneously made.
Make corrections after confirming the wiring.
External command and position command is not
inputted.
Confirm the wiring of input terminal and input it
correctly.
Servo-ON is not made.
The allotted parameter of sequence input signal
(Ft-0.10) shall be confirmed for setting.
The selection of command pulse is wrong.
Refer to Chapter 5-10 page "Position Control
Mode" and correctly set it.
Over trouble input is turned off.
P-OT, N-OT input signal is made to ON.
It is in overload condition.
Release the overload condition and operate it.
Servo alarm occurs.
Remove the cause for alarm and implement the
alarm reset then re-start it.
Motor vibrates or has large
overshoot in accelerating or
decelerating.
The speed loop integration gain of servo is too
high.
Lower the system gain [Ft-1.01]. Heighten the
speed loop integration gain [Ft-1.03].
The motor rotates at the speed
command ‘0’.
The speed command offset adjustment is
erroneously made.
In put ‘0’ to the speed command and redo the
offset adjustment.
The encoder type setting error
or encoder circuit alarm occurs.
The setting of motor and encoder is erroneous.
Confirm the motor setting parameter [Ft-0.01],
and then set it correctly.
Motor and encoder wiring is erroneous.
Refer to the wiring in Chapter 3 and make a
correction.
Strange noise is made.
Mechanical installation condition is bad.
Confirm the installation condition (coupling, nut
tightening) and adjust.
Motor or drive is overheated.
The ambient temperature is high.
Lower the ambient temperature. (under 50 [°C] )
It is in overloaded condition.
Release the overload condition and operate it.
CSD5 Servo Drive