Fault messages
If a fault is indicated by the signal ring of the control unit flashing red, a fault code is displayed
via the Wolf-control accessory with eBUS capability that allows a cause to be allocated using
the following table.
This list of fault messages is designed to allow your heating contractor to trace the fault more
easily.
Note: Faults that are not listed may be faults of the air-condition or ventilation control.
No.
62
Fault
Cause
1
TB excess temperature
The external temp. limiter has shut down the system.
4
No flame established
No flame established during the burner start
5
Flame failure during
Flame failure during the safety time
6
TW excess temperature
The boiler water temp. has exceeded the limit
for the TW (e.g. 95 °C)
7
STBA - excess temperature
The temperature limiter has shut down the system
8
No flue gas damper response Flue gas damper or damper feedback faulty
11
False flame indication
A flame is recognised before the burner starts
12
Boiler sensor faulty
The boiler water temp. sensor or sensor lead is faulty
13
Flue gas temp. sensor faulty
The flue gas sensor or sensor lead is faulty
14
Cylinder sensor faulty
The DHW temp. sensor or sensor lead is faulty
15
Outside temperature sensor
faulty
The outside temperature sensor is faulty (short
circuit or break, wireless reception interference,
battery of the wireless outside temperature sensor
dead), power supply boiler interrupted or boiler
fuse blown / tripped
16
Return sensor faulty
The return sensor or the sensor lead is faulty
17
Fault modulation current
The modulation current is outside its set range
20
Faulty gas valve V1
The gas valve is faulty
21
Faulty gas valve V2
The gas valve is faulty
22
Lack of air
The air pressure switch does not switch ON
23
Faulty air pressure switch
The air pressure switch does not switch OFF
24
Gas fan, fault
The gas fan does not reach the required
pre-purging speed
25
Gas fan, fault
The fan does not reach the ignition speed
26
Gas fan, fault
The fan does not stop
30
CRC fault, boiler
Internal device error
31
CRC fault, burner
Internal device error
32
Power failure 24 V
24 V power supply faulty